Circuit Load Calculator
EngineerCalculate circuit current from total fixture wattage, see breaker utilization and the maximum number of fixtures a circuit can carry.
W
Voltage
Phase
Breaker Rating
If the driver's power factor isn't specified, 0.9 is a common default.
- Circuit Current
- 9.66 A
- Utilization
- 75.5%
- Max Continuous Current (80%)
- 12.8 A
Within limit
Fixture Count Calculation
W
This circuit can carry up to 66 fixtures.
The total power on a lighting circuit must not exceed what its breaker can safely carry. This tool calculates circuit current with I=P/(V·PF) for single phase or I=P/(√3·V·PF) for three phase, then shows utilization against the commonly used "80% rule" for continuous loads (80% of the breaker's rated current). You can also enter the wattage per fixture to see how many fixtures a circuit can carry. The 80% figure and breaker selection should ultimately follow your local electrical code.